Measurement & Control of just about anything

Measurement & Control of just about anything

g3title

Now supports Modbus Slave protocol!

If you need to control or monitor a device or system at a distance, the G3 is the solution. It comes complete with 8 x onboard I/O that allow you to connect to almost any device. Use it monitor or control pumps, valves, PLCs, dataloggers, rain gauges, tank levels, security systems, fire & evac systems, access control, irrigation systems, flow meters, emergency standby systems and more.sale.png

The G3 uses license free spread spectrum (900Mhz or 2.4Ghz), so you can get your remote monitoring or control application up and running fast.

For a limited time, we are offering the G3 system at a low introductory price. Please contact Maximation for more information

Suitable for all Industries!

  • Factories
  • Security Systems
  • Mining
  • Water & Wastewater
  • Building Management
  • Mobile plant & equipment
  • Agriculture
  • Aquaculture
  • Transport monitoring
  • Fire systems
  • Race tracks
  • Event management
  • Emergency services and many more...
g3brochure

Download the brochure..click here

8io 

Product features

g3sm
stopwatchsm
g3ledsm
lock
terminal
Multi Function display
Event logging
System status LEDs
Security enabled
Onboard wiring terminals

with navigation keys for easy on site display of values or diagnostics.

capture events as they happen with time/date stamping.

4 x Status LEDs report system status at a glance

Password protected menus and secure spread spectrum communications.

Removable socket design allows for easy wiring installation

usb
logicsm
relaysm
Option-R-CP-11Transparent
g3man
Mini USB connector
Logic functions
Onboard I/O
Wireless comms
Free software utility
for programming via laptop/PC.
Inbuilt logic functions allow basic control of inputs and outputs/
Total of 8 x I/O allow you to connect to almost any device. (2 x AI, 2 x AO, 2 x DI, 2 x DO)
License free spread spectrum technology allows to connect to remote system with ease.
G3Manager allows you to setup the G3 using your Windows PC. Event logs can also be downloaded from the G3 for archiving.

4 Different operating modes to suit every application

Stand Alone Mode

Stand alone mode allows you to control a device locally using the inbuilt logic functions. In this mode the G3 functions as a small logic controller, allowing you to control devices / systems with event logging capability.

standalone 

Back to Back Mode

Back to Back mode allows you to use the G3 as a wire replacement device. Ideal for when you need to monitor or control a device remotely, where cabling would prove too difficult or costly.

backtoback 

Remote I/O Mode

Remote I/O mode allows you to connect over 200 G3 devices to your Kingfisher Series II or III telemetry system. Perfect for when you need to monitor or control remote devices with your SCADA system.

remoteio 

Modbus Slave Mode

Firmware update for G3 now includes support for Modbus slave protocol. This allows the G3 to interface to a wider range of devices such as HMIs, PLCs, SCADA PCs, RTUs (Kingfisher and other brands). The Modbus master can communicate to the G3 using a stand-alone Maxstream Spread Spectrum modem.

Modbus direct to SCADA PC Modbus direct to operator panel (HMI)

Direct to SCADA PC using Modbus

Direct to Operator Display (HMI) using Modbus

Modbus direct to PLC Modbus direct to RTU

Direct to PLC using Modbus

Direct to RTU (Kingfisher and other brands) using Modbus

g3range
 

Product Specifications

Processing

uProcessor Type TI MSP430 (16-bit)
Memory Flash + RAM 48KB+10KB

Communications

Wireless comms (optional) License-free frequency-hopping Spread Spectrum (900MHz & 2.4GHz)
Communications Strategy RBE (Report-By-Exception) & Polled. User configurable
Transmit Power
(Spread Spectrum)
900MHz - 1W
2.4GHz - 50mW
Line of sight range
(Spread Spectrum)
Subject to local conditions and antenna selection900MHz - up to 20 Miles / 32 Kms2.4GHz - up to 5 Miles / 8 Kms
Reciever Sensitivity
(Spread Spectrum)
900 MHz -110 dBm 2.4 GHz -105 dBm
Frequency
(Spread Spectrum)
900 US/CAN: ISM 902 - 928 MHz900 AU: ISM 915 - 928 MHz
2.4: ISM 2.4000 - 2.4835 GHz
Data rate (Spread Spectrum) Normal 9600bps. High Speed Mode 115K/bps
 

I/O Capability

Analog Inputs Two 0-20mA or 4-20mA inputs. 12 bit resolution. Terminating resistance: 100Ω. Input inpedance 250Ω.
Over current and over voltage protected. Surge and transient protected
Analog Outputs Two 0-20mA or 4-20mA outputs. 12 bit resolution. Maximum load 1275Ω@30V
Designed for field voltages of 9V to 30V. Over and reverse voltage protected. Surge and transient protected
Discrete Inputs Two inputs accepting levels up to 24V, with a low to high threshold of approx 2.5V. Surge and transient protected
Discrete Outputs Two open collector outputs, switch voltages of up to 30V to ground.
Switched supply voltage is available for driving inputs and outputs. Surge and transient protected
I/O Failsafe Yes. Programmable failsafe setpoints on all Analog and Digital outputs
   

Onboard Display

Onboard display 96 x 64 pixel OLED with navigation keysShows status, I/O values, configuration details, etc
Status LEDs 4 x Status LEDs. Power, Scan, Comms, and Error
Control mode Yes, user can toggle/change inputs and outputs via front keypad for testing purposes
   

Power

Supply Voltage 9 to 30V DC, nominally 12V or 24V.Fuse protected (1A resettable). Over and reverse voltage protected. Input voltage is monitored
Supply Current (@12 Vdc) Up to 400mA TX On, 20mA operating, <5mA in sleep mode
Output power Supply voltage up to 200mA
 

General

Programming port Mini USB 2.0 port for configuration and diagnostics. ESD protected to 20kV
Operating modes Stand alone, Back to Back, Remote I/O (maximum 249 devices per SCADA host)
Real Time Clock (RTC) Yes, onboard realtime clock
Security Password protected menus, encrypted communications and configurable Network ID
Event logging Last 1000 events with time and date stamping
Counters 2 x General purpose 32 bit counters with programmable events for use in functions
 

Programming

Programming Software Kingfisher G3Manager configuration and programming software
Environment
Environmental -40oC to +70oC (-20oC to +70oC for OLED display)
Relative Humidity 5 - 95% Non-condensing
Approvals FCC, CE, C tick