Login
 
Home arrow Products arrow Kingfisher Series IIarrow Processor modules
 
MC-11 Multi communications module

Features:

The multi communications module for the Series II Remote Terminal Unit provides additional ports in any RTU configuration. This module has up to three independent communications ports. Ports 2 and 3 may use optional plug-in option boards while port 1 is fixed as RS232C.

This module consumes power from the +5VDC bus on the backplane. It also requires to +12VDC. Up to five MC-10/11 modules can be installed in any I/O slot of a 4, 6 or 12 slot backplane. An RTU may have up to a total of 16 ports.

  • Multi Communication module for Series II RTUs
  • Provides an additional 3 ports for more connectivity
  • Port 1 RS232C, Ports 2 & 3 suitable for Communication option boards
  • Advanced Intel CPU, 25MHz
  • 1MB RAM
  • MC-11-xx (Multi Communication Module c/w 1xRS232 port + 2 x option ports)
  • Note: xx denotes that the multi-communcation module can be delivered with up to 2 option boards preloaded at time of shipping. Please advise your Kingfisher dealer if you require any option boards preloaded.

    Example: MC-11-DF

    MC-11 fitted with Option D (Dial up modem) and Option F (Fibre Serial)

    Product Specifications:

    General
       
    Processor Intel 80C386EX
    Word Size 32 Bit internal data bus
    16 Bit external data bus
    Clock Speed 25MHz
    BIOS
    Y
    FLASH RAM 1MB
    Static CMOS RAM 1MB
    RTC Y
    WDT Y
    Status Indication Y
    Communication Ports 1-3 (1 fixed, 2 option ports)
    Port 1 (RS232) 300 to 115200 Baud
    Port 2 (Optional) Not fitted, RS232 only, RS232/RS485/RS422, PSTN, PLINE, Radio + more
    Port 3 (Optional) Not fitted, RS232 only, RS232/R485/RS422, PSTN, PLINE, Radio + more
    Configuration Software Toolbox
    Diagnostics Software Y
    Communications Protocol Kingfisher, Modbus RTU + many more
    MC-10/11s per RTU 5
    Internal Power Consumption 275mA from +5VDC bus on backplane
    CM Bus Data Rate 83.3/250 KBit/s
       
    Environmental
       
    Operating Temperature -20C to 70C / -4F to 158F
    Storage Temperature -40C to 85C / -40F to 185F
    Operating Humidity 5 to 98% RH non-condensing

    Recommend Print Datasheet