Features:
The line option board provides a Private Line or Radio interface and is software configurable for either of these modes. There are two revisions of the line option board.
The original revision 'LINE-L' had a configurable output level (using Toolbox software). The newer revision 'LINE-2' has a fixed output level. Both have the same specifications.
- Private/Line radio interface board
- Fits CP-10, CP-11, CP-21, CP-30,?MC-10, MC-11, LP-1
COMMS-OPTION-L (2/4 Wire Line for CP-11/CP-21/MC-11, option port 2/3)
|
Product specifications: |
|
General
|
| |
| Baudrate |
1200 Baud |
| Modulation |
FSK, CCITT V.23 |
| Carrier detect input |
Optical isolation
Active low or high
Min. input 2mA (70VDC max.) |
RTS/PTT output
Microwave networks typically use a negative supply rail for the carrier detect circuit. The more positive rail should be connected to pin #6 (RTS/PTT) and the difference between the rails must not exceed 30VDC. |
Optical isolation
Open collector output
Active low
30VDC max. at 20mA max. |
| Output impedance |
30 K ohm |
| Input impedance |
30 K ohm |
| Line termination |
600 ohm |
| Line configuration |
2 or 4 wire
The port is not full duplex and cannot use the full duplex functionality of a 4-wire configuration. 4-wire configurations eliminate the ability to communicate peer to peer but allow an increased number of drops on one link. |
| Line drive in multidrop configuration |
10 drops for 2 wire
20 drops for 4 wire |
| Transmit output level |
-6 dBm (LINE-2)
-6 to -21 dBm software configurable (LINE-L) |
Receive level |
-43dBm to -9dBm |
Transmission Distance |
Allowing 3dB for background noise and a 10dB fade margin, up to 24dB of cable loss can be tolerated. Therefore, transmission distance = 24 / cable loss per Km (dB).
Note: if there are more than 2 RTUs (or other devices) on the line, reduce the allowable cable loss (24) by 1dB per additional RTU or device. |
| Configuration Software |
Toolbox |
| Internal Power Consumption |
85 mA from +5VDC Bus on backplane |
| Isolation |
3.88 kV |
| |
|
|
Environmental
|
| |
|
| Operating Temperature |
-20C to 70C / -4F to 158F |
| Storage Temperature |
-40C to 85C / -40F to 185F |
| Operating Humidity |
5 to 98% RH non-condensing |